Scope
This standard covers test methods and performance values for metal-oxide varistor (MOV) surge protective components (SPCs) with the following main parameter ranges: Packaging: Leaded disc-type or surface mount; Nominal varistor voltage: 5 V to 1200 V; 8/20 surge current rating: 10 A to 70 kA; 8/20 clamping voltage: 10 V to 3 kV. With appropriate component selection, these components could be used for the overvoltage protection of power and signal systems having the following: Continuous ac voltages: 2.5 V rms to 750 V rms; Steady-state dc voltages: 3.3 V to 1000 V; Peak signal feed voltages: 3.5 V to 850 V.Information is given on manufacturer type testing used to determine environmental performance and ratedvalues.Purpose
This document will not contain a purpose clause.Abstract
Revision Standard - Active.Test methods and preferred values for metal-oxide varistor (MOV) surge protective components are covered in this standard and have the following main parameter ranges: packaging (leaded disc-type or surface mount), nominal varistor voltage (5 V to 1200 V), 8/20 surge current rating (10 A to 70 kA), and 8/20 clamping voltage (10 V to 3 kV). With appropriate component selection, these components could be used for the overvoltage protection of power and signal systems having continuous ac voltages (2.5 V rms to 750 V rms), steady-state dc voltages (3.3 V to 1000 V), and peak signal feed voltages (3.5 V to 850 V). Information is given on manufacturer type testing used to determine environmental performance and rated values. Product Details
Published: 01/29/2018 ISBN(s): 9781504438025, 9781504438032, 9781504446716 Number of Pages: 41File Size: 1 file , 2.3 MB Product Code(s): STD22454, STDPD22454, STDPL22454